Size a well pressure tank by drawdown, the usable water it delivers between pump cycles. Multiply the pump’s flow in gallons per minute (GPM) by the motor manufacturer’s minimum run time. Then choose a tank whose published drawdown meets that target at your pressure switch settings. A 10 GPM pump that needs a one-minute run time calls for at least 10 gallons of drawdown.
This guide explains how the pump, tank and switch work together. It also covers drawdown, precharge and signs that a tank may be undersized or failing. If you are replacing the pump, compare the Sta-Rite jet pumps in our well pump collection.
How a Well Pump, Pressure Tank, and Pressure Switch Work Together
The switch starts the pump when system pressure drops to the cut-in setting. The pump refills the tank until pressure reaches cut-out. The tank then supplies water between cycles.
- Cut-in: when you use water and pressure drops to the lower switch setting (for example 30 psi on a 30/50 switch), the switch starts the pump.
- Refill: the pump pushes water into the tank, compressing the air charge above or around the water.
- Cut-out: when pressure reaches the upper setting (50 psi on a 30/50 switch), the switch stops the pump.
- Drawdown: you use stored water as pressure falls from cut-out back to cut-in. That usable volume is the tank's drawdown.
Common switch settings are 20/40, 30/50, and 40/60. Sta-Rite shallow well jet pumps, for example, ship with a 30/50 switch. A higher setting gives stronger pressure at the tap but slightly less drawdown from the same tank.
Drawdown vs Tank Size: Why a 20 Gallon Tank Isn't 20 Gallons
Nominal size is the tank’s total volume. Drawdown is the smaller volume you can use before the pump starts again. Amtrol’s Well-X-Trol charts show how drawdown varies with tank size and pressure settings.
|
Nominal tank volume |
Drawdown at 30/50 psi |
Drawdown at 40/60 psi |
|---|---|---|
|
20 gal |
6.2 gal |
5.4 gal |
|
32 gal |
9.9 gal |
8.6 gal |
|
44 gal |
13.6 gal |
11.8 gal |
|
62 gal |
19.2 gal |
16.6 gal |
|
81 gal |
25.0 gal |
21.7 gal |
|
119 gal |
36.8 gal |
31.9 gal |
That works out to roughly 31% of nominal volume at 30/50 and about 27% at 40/60. Other brands publish similar charts, so always check the drawdown figure for the exact tank and setting you plan to use.
The Minimum Run-Time Rule
Starting a motor creates heat. Franklin Electric’s guidance calls for a minimum run time to help dissipate it. Check the requirement for your specific motor and controller. Some applications need more than one minute.
Required drawdown in gallons equals pump flow in GPM multiplied by minimum run time in minutes. Use the motor manufacturer’s requirement for the calculation.
How to Size a Pressure Tank for a Well Pump
- Use the pump curve at the system’s operating head to estimate flow. Include well lift, pressure and friction losses. A jet pump’s advertised maximum flow will usually exceed what it delivers at the actual duty point.
- Pick your minimum run time. One minute is the common minimum. Check your pump and motor manual.
- Multiply to get required drawdown. A 10 GPM pump at one minute needs about 10 gallons of drawdown.
- Read the tank chart at your switch setting. Choose a tank whose drawdown at 30/50 or 40/60 meets or beats that number.
- Round up to a tank with sufficient published drawdown. A tank with too little drawdown can cause the pump to start more often than the motor manufacturer allows.
Pressure tank size for well pump: quick guide by GPM
This table applies the one-minute rule to the Amtrol drawdown ratios above. Treat it as a guide only and confirm against the specific tank's published drawdown.
|
Pump flow |
Drawdown needed (1 min) |
Approx. tank class at 30/50 |
Approx. tank class at 40/60 |
|---|---|---|---|
|
5 GPM |
5 gal |
20 gal |
20 gal |
|
7 GPM |
7 gal |
32 gal |
32 gal |
|
10 GPM |
10 gal |
44 gal |
44 gal |
|
12 GPM |
12 gal |
44 gal |
62 gal |
|
15 GPM |
15 gal |
62 gal |
62 gal |
|
20 GPM |
20 gal |
81 gal |
81 gal |
If you want two minutes of run time, double the drawdown and step up the tank, or use two tanks plumbed together. Multiple tanks add their drawdown.
Matching a Pump to Your Existing Tank?Tell us your switch setting, tank size, and well depth and we will help you pick a pump that fits. Call (844) 378-6771 or browse our shallow well jet pumps. |
Setting the Precharge
Precharge is the tank’s air pressure with the water side drained. For the conventional systems described here, Amtrol and Sta-Rite specify 2 psi below the switch’s cut-in pressure. Follow the instructions for your exact tank and controller.
|
Switch setting (cut-in/cut-out) |
Precharge |
|---|---|
|
20/40 |
18 psi |
|
30/50 |
28 psi |
|
40/60 |
38 psi |
- Turn off power to the pump.
- Open a faucet and drain the system until pressure reads zero, so the tank is empty of water.
- Check the air valve on the tank with a tire gauge.
- For a tank in sound condition, follow the manufacturer’s procedure for adjusting precharge. Close the drain and restore power only after completing the checks in the manual.
Check the factory setting before startup. If an installed tank has lost its air charge, shows corrosion or suddenly cycles more quickly, have it inspected before adding air.
Diaphragm or Bladder Tanks vs Air-Over-Water (Galvanized) Tanks
|
Diaphragm or bladder tank |
Air-over-water (standard galvanized) |
|
|---|---|---|
|
How it works |
A flexible membrane separates the air charge from the water |
Air and water share the tank with no barrier |
|
Air loss |
Minimal; the charge stays put if the membrane is intact |
Air slowly dissolves into the water and must be replaced |
|
Extra hardware |
None beyond the air valve |
Usually an air volume control or other air-charging method |
|
Size for same drawdown |
Smaller |
Larger |
|
Typical use today |
Most new residential well systems |
Older systems and some specialty installs |
Most new well pump with pressure tank installs use a precharged diaphragm or bladder tank. If you have an older galvanized tank that keeps waterlogging, switching to a precharged tank is a common upgrade.
Signs Your Pressure Tank Is the Wrong Size or Failing
- Short cycling: the pump clicks on and off every few seconds while water runs. The tank is undersized, the precharge is low, or the tank is waterlogged.
- Water at the air valve of a bladder tank can indicate that the membrane has failed. Have the tank inspected before trying to recharge it.
- Pressure swings at the tap: rapid jumps between strong and weak pressure.
- Low system pressure: the tank cannot hold pressure between cycles. See why a well pump loses pressure.
- Pump runs too long or never shuts off: often a pump or switch problem rather than the tank, covered in 8 signs your well pump is going bad.
Jet Pump vs Submersible: Tank Notes
An aboveground jet pump, tank and switch are often installed together in a basement or pump house. Protect all three from freezing, as explained in our well pump freeze protection guide. Use the pump curve at the actual system head to size the tank.
The same drawdown calculation applies to a conventional deep-well system. Check the motor’s run-time and starting limits before choosing the tank. For pump selection, see jet pump vs submersible pump, compare deep well pumps and use our 1 HP vs 2 HP sizing guide.
Booster Pump and Pressure Tank
A booster pump raises pressure on an existing supply. A small tank can reduce starts from brief draws. Check the booster manufacturer’s inlet pressure, supply flow and tank sizing requirements. Constant-pressure systems often use a smaller tank sized to the controller manufacturer’s instructions. See VFD vs fixed speed pump systems or browse our pressure pumps collection.
Does ePumps Sell Pressure Tanks?
ePumps can help match a Sta-Rite well pump to the tank you have or plan to buy. Have the tank model, published drawdown, switch settings and well details ready when you contact us.
Final Thoughts
Find the pump’s flow at the actual operating head and multiply it by the motor’s required minimum run time. Use the tank chart to confirm drawdown at your switch settings, then follow the manufacturer’s precharge instructions. For help selecting a pump, see our best well pump picks.
Frequently Asked Questions
What size pressure tank do I need for my well pump?
Multiply the pump’s flow in GPM by its required minimum run time in minutes. Choose a tank whose published drawdown at your pressure switch settings meets or exceeds that volume.
What should the pressure tank be set at for a 40/60 switch?
For a conventional tank whose manufacturer specifies 2 psi below cut-in, a 40/60 switch calls for 38 psi of precharge. Check it with power off and the water side drained.
Can a pressure tank be too big for a well pump?
A larger tank mainly means longer, fewer pump cycles, which is easier on the motor. The limits are space, weight, and how long water sits in the tank, so most installers size to the drawdown target and round up one step.
Why does my well pump turn on and off so fast?
Rapid cycling usually means the tank is undersized, the precharge is too low, or a bladder tank is waterlogged. Check the precharge with the tank empty; if water comes out of the air valve, the tank likely needs replacement.
Get the Right Pump for Your TankCall the ePumps team at (844) 378-6771 or contact customer service with your tank size and switch setting, and browse all well pumps. |