To size a Grundfos pressure pump, calculate the building’s peak flow and the pressure the pump must add at that flow. A horizontal CM is often a good starting point for smaller flows and moderate boost. A vertical CR typically covers higher flows or greater pressure requirements.
This guide shows how to calculate your duty point, compare CR and CM pumps, and check inlet conditions and drinking water certification. If you already know your duty point, browse our Grundfos pumps.
What Does a Grundfos Pressure Pump Do?
A pressure booster raises the pressure of an existing water supply. Grundfos offers two multistage centrifugal pump families commonly used for boosting in buildings, agriculture, and light industry.
- CR (vertical multistage): inline suction and discharge ports, a small footprint, and a wide flow and pressure range. Available as CR, CRI and CRN for different materials.
- CM (horizontal multistage): a compact close-coupled design for smaller flows, common in light commercial and residential boosting.
Our Grundfos CR vs CM comparison covers construction and operating ranges. For an introduction, see what is a pressure pump and what is a booster pump.
Step 1: Work Out Your Peak Flow
Size the booster for peak demand. The calculation depends on how the building or equipment uses water.
- Plumbing systems: peak demand is normally calculated from fixture units using the method in your local plumbing code. Your engineer or plumber will have this figure on the drawings.
- Process or equipment supply. Add the flow requirements of equipment that can operate at the same time.
- Irrigation. Use the flow of the highest-demand zone if the zones run individually. If zones can run together, use the highest combined demand.
- Replacing an existing booster. Use the old pump’s nameplate and curve as a starting point. Verify them against current demand and supply pressure.
Record peak flow in gallons per minute (gpm). It is the flow component of your duty point.
Step 2: Work Out the Boost Pressure
Calculate the pressure needed at the most demanding outlet, then work back to the pump.
- Required outlet pressure. Use the minimum pressure specified by the fixture or equipment manufacturer and account for applicable code requirements.
- Elevation. Add 0.433 psi for every foot the highest outlet sits above the pump.
- Friction losses. Add the pressure lost through pipe, fittings, meters, backflow preventers and valves at peak flow.
- Subtract the minimum incoming pressure. Use the minimum expected pressure at the pump inlet under peak-flow conditions.
The difference is the required boost. For water, multiply psi by approximately 2.31 to convert the boost pressure to feet of head.
A Worked Example
This example uses illustrative values for a small building. Use your own design flows and supply pressures when sizing a pump.
|
Item |
Value |
Notes |
|---|---|---|
|
Peak flow |
40 gpm |
From fixture unit calculation |
|
Pressure needed at top fixture |
35 psi |
Fixture maker's minimum |
|
Elevation to top fixture |
60 ft = 26 psi |
60 x 0.433 |
|
Friction and fittings at peak flow |
10 psi |
From pipe sizing |
|
Total pressure needed at pump discharge |
71 psi |
35 + 26 + 10 |
|
Minimum incoming pressure |
40 psi |
Minimum at the pump inlet at design flow |
|
Boost required |
31 psi = about 72 ft |
31 x 2.31 |
The duty point is approximately 40 gpm at 72 feet of head. Compare Grundfos curves for a model that meets that point within its recommended operating range. Our guide on how to read a pump curve shows how to plot it.
Know your duty point and need help choosing a model?Send us your peak flow, required boost pressure, and supply voltage for help selecting a Grundfos CR or CM pump. Call (844) 378-6771 or reach our team. |
Step 3: Choose Between CR and CM
Use your duty point to compare individual CR and CM curves. The first number in the model designation identifies the nominal flow size in cubic meters per hour. The number after the dash indicates the stage count. Our Grundfos model numbers guide explains the full code.
|
If your system looks like this |
Start with |
Why |
|---|---|---|
|
Small flows, moderate boost, tight space |
CM (CM1 to CM25) |
Compact horizontal unit, simple to mount on a skid or floor |
|
Medium to large flows or high boost |
CR (CR1 to CR64 in our range) |
More stages and larger frames reach higher pressures and flows |
|
Water that attacks cast iron |
CRI or CRN |
Stainless steel construction options for different water chemistries |
|
Tall building with high boost requirements |
CR |
Higher stage counts can provide the head needed to overcome elevation and friction |
Browse the Grundfos CR series or the horizontal multistage pressure pumps collection, which carries our CM range. For a deeper look at the CM, see our Grundfos CM booster pump buying guide.
Step 4: One Pump or Several?
A single pump is the simplest arrangement. A multiple-pump system can provide backup capacity or better accommodate wide swings in demand.
- Duplex (two pumps). Size each pump for the full peak if either must meet demand on its own. If both are needed at peak flow, a single pump can provide only partial service during an outage.
- Triplex and larger systems. Pumps come on in stages as demand rises, helping the running pumps stay within their preferred operating range.
- Variable speed. A drive adjusts pump speed as demand changes to maintain the discharge pressure setpoint. It can reduce energy use and pressure fluctuations in suitable systems.
Our post on VFD pump systems vs fixed speed pumps explains when a drive pays for itself, and the control panels and VFDs collection has the drives and panels we stock. For the redundancy question, see simplex vs duplex pump systems.
Step 5: Check the Inlet Side
Standard CR and CM pumps require priming before startup. Check that the inlet can provide enough pressure at design flow.
- Provide a reliable inlet supply. For a break tank, check that the minimum operating water level provides adequate suction head. For a pressurized supply, check the minimum pressure at peak flow.
- Protect against low inlet pressure. A low-pressure switch or low-level cutoff can stop the booster if the water supply falls below its operating limit.
- Check the maximum inlet pressure. Incoming pressure plus the pump's own pressure at zero flow must stay within the pump's rated working pressure.
- Add a pressure tank to limit cycling. On a fixed speed booster, a correctly sized tank stops the pump starting and stopping every time someone opens a tap.
Step 6: Drinking Water and Temperature
For potable water, verify that the exact model is certified for drinking water and that the service temperature falls within the certification. Also confirm that the pump materials and seal are suitable for the liquid and temperature. Our CR vs CRI vs CRN guide compares the material options.
Common Sizing Mistakes
- Sizing from horsepower. Two pumps with the same motor can deliver very different flow and pressure. Always size from the duty point.
- Using average supply pressure. The booster has to perform at the lowest incoming pressure, typically during peak demand in the neighborhood.
- Adding excessive sizing margin. An oversized booster can operate outside its preferred range, cycle more often, or deliver excessive pressure if the controls are set incorrectly.
- Forgetting the low floors. In tall buildings, the pressure that serves the top floor can be too high for the bottom. Pressure reducing valves on lower zones may be needed.
If an existing booster is already giving trouble, our Grundfos CR troubleshooting guide covers pressure, noise and cycling problems.
Final Thoughts
Use peak flow and the minimum inlet pressure at that flow to calculate the required boost. Compare CR and CM pump curves, then verify inlet conditions, controls, and any potable water certification. Our Grundfos centrifugal pumps explainer covers how multistage pumps develop head. For steam boiler applications, see our guide to Grundfos boiler feed pumps.
Frequently Asked Questions
What is a Grundfos pressure pump?
A Grundfos pressure pump boosts water pressure in a building, irrigation system, or process line. The CR and CM are two multistage centrifugal pump families used for this purpose.
How do I size a booster pump for a building?
Determine peak flow in gpm. Add the required outlet pressure, elevation allowance (0.433 psi per foot for water), and friction losses. Subtract the minimum inlet pressure at design flow, then multiply the required boost in psi by about 2.31 to convert it to feet of head.
Should I choose a Grundfos CR or CM booster pump?
Start with a CM for smaller flows and moderate boost, or a CR for higher flows or higher boost. Confirm the selection on the pump curve. Consider CRI or CRN if water chemistry calls for stainless steel.
Can a Grundfos booster pump be used for drinking water?
Yes. Choose a model certified for potable water and verify that the certification covers the intended service temperature.
Ready to choose your Grundfos pressure pump?Browse our Grundfos pumps or call (844) 378-6771 for help choosing a CR or CM model. |